Fluke 433 and 433 Power Quality Analyzer Functions
Function: Scope - Phasor
The Scope function provides a clear view of current and voltage waveform shapes. Voltage waveforms in particular should be smooth and sinusoidal. If you see voltage distortion on the waveform, check the harmonics display. The RMS voltages and frequency should be close to their nominal values.
Waveform and Phasor display are also a useful way to verify that voltage leads and current clamps are connected correctly. In the vector diagram, ensure that the phase voltages and currents L1 (A), L2 (B), and L3 (C) appear in sequence when observing them in clockwise direction.
To access, push the Scope button. Then, push F3 for Phasor.

Function: V-Amps-HZ
Voltage and frequency should be close to the applicable nominal values: 120 V, 230 V, 480 V, 60 Hz, or 50 Hz. For example: Check the voltages and currents in the table to see if power applied to a three phase induction motor is in balance. Each of the phase voltages should not differ more than 1 % from the average of the three. Current unbalance should not exceed 10 %. Voltage unbalance causes high unbalanced currents in stator windings, resulting in overheating and reduced motor life. If unbalance is too high, use other measuring modes to further analyze the power system. A Crest Factor close to 2.0 indicates high distortion. A pure sine wave would have a crest factor of 1.414. Anything higher is a result of distortion.
To access, push the Menu button and select Volt/Amps/Hertz.

Function: Dips & Swells
Dips (Sags) and Swells may indicate a weak power distribution system. In a weak system, voltage will change considerably when a big motor or a welding machine is switched on or off. This may cause lights to flicker or even show visible dimming. It can also cause reset and data loss in computer systems and process controllers. By monitoring the voltage and current trend at the power service entrance, you can determine if the cause of the voltage dip is inside or outside the building. The cause is inside the building (downstream) when voltage drops while current rises; it is outside (upstream) when both voltage and current drop.
To measure dips and swells, push the Menu button and select Dips & Swells.

Function: Harmonics
The harmonic number indicates the harmonic frequency: the first harmonic is the fundamental frequency (60 or 50 Hz), the second harmonic is the component with two times the fundamental frequency (120 or 100 Hz), and so on. The harmonics sequence can be positive (+), zero (0), or negative (-).

Harmonic Frequencies and Sequences
Order 1st 2nd 3rd 4th 5th 6th
Frequency 60 Hz
50 Hz
120 Hz
110 Hz
180 Hz
150 Hz
240 Hz
200 Hz
300 Hz
250 Hz
360 Hz
300 Hz
Sequence + - 0 + - 0

As you can see, the sequence is + - 0 + - ….
Positive sequence harmonics try to make a motor run faster than the fundamental; negative sequence harmonics try to make the motor run slower than the fundamental. In both cases the motor loses torque and heats up. Harmonics can also cause transformers to overheat. Even harmonics will disappear if waveforms are symmetrical, i.e. as equally positive and negative. Zero sequence current harmonics add in Neutral conductors. This can cause these conductors to overheat.
Current distortion is expected in a system with non-linear loads like DC power supplies. When the current distortion starts to cause voltage distortion (THD) of more than 5 %, this signals a potential problem.
K-factor indicates the amount of harmonic currents and can help in selecting transformers. Use K-factor along with apparent power (kVA) to select a replacement transformer to handle non-linear, harmonics-rich loads. K-factor is a mathematically derived value that takes into account the effects of harmonics on transformer loading and losses. A K-rated transformer is one that is specifically designed to handle the effects associated with higher levels of harmonics.
To measure Harmonics, push the Menu button and select Harmonics. To measure K-factor, select Power & Energy.

Function: Power & Energy
Power mode can be used to record apparent power (kVA) of a transformer over several hours. Look at the Trend and watch for periods or peaks that exceed the rating of the transformer. To mitigate the overload, transfer loads to other transformers, stagger the timing of loads, or install a larger transformer. Interpretation of Power Factor when measured at a device: PF = 0 to 1: not all supplied power is consumed, a certain amount of reactive power is present. Current leads (capacitive load) or lags (inductive load). PF = 1: all supplied power is consumed by the device. Voltage and current are in phase. PF = -1: device generates power. Current and voltage are in phase. PF = -1 to 0: device is generating power. Current leads or lags.
If you see negative power or power factor readings and you are connected to a load, check to make sure the arrows on your current clamps are pointing towards the load. Reactive power (VAR) is most often due to inductive loads such as motors, inductors, and transformers. Installing correction capacitors can correct for inductive VARs. Check with a qualified engineer before adding PF-correction capacitors, especially if your system is already carrying current harmonics.
To access power mode, push the Menu button and select Power & Energy.

Function: Flicker
Flicker refers to rapid change (to fast to see) in overhead lightning resulting in human visual annoyance, headaches and eye-strain. From the Flicker function, use the PF5 flicker trend and half-cycle voltage or current trends to find the source of flicker. Press function key F1 to assign the arrow keys to flicker, voltage, and current trends. Use a 10 minute (PST) measuring period to eliminate the influence of random voltage variations and detect interference from a single source with a long working cycle, such as household appliances and heat pumps. A two hour measuring period (PLT) is useful when facing more than one interference source with irregular working cycles and for equipment such as welding machines and rolling mills.
To access, push the Menu button and select Flicker.

Function: Unbalance
The voltages and currents in the Unbalance table can be used to check if applied power is in balance; for example, on a three phase induction motor. Voltage unbalance causes high unbalanced currents in stator windings, resulting in overheating and reduced motor life. Each of the phase voltages should not differ more than 1 % from the average of the three. Current unbalance should not exceed 10 %. If unbalance is too high, use other measuring modes to further analyze the power system. Each phase voltage or current can be split into three components: positive sequence, negative sequence, and zero sequence. The positive sequence is the normal component present in balanced 3- phase systems. The negative sequence results from unbalanced phase-to-phase currents and voltages. For instance, this component causes a 'braking' effect in three phase motors, resulting in overheating and life reduction. Zero sequence may appear in an unbalanced load in 4 wire power systems and represents the current in the N (Neutral) wire. Unbalance exceeding 2 % is considered too high.
To access, push the Menu button and select Unbalance.

Function: Transients
Transients in a power distribution system can cause many types of equipment to malfunction. Equipment subjected to repeated transients can eventually fail. Events occur intermittently, making it necessary to monitor the system for a period of time to locate them. Look for voltage transients when electronic power supplies are failing repeatedly or if computers reset spontaneously. To isolate the fault location, use the Transients function and monitor at several points in the distribution. As you work your way down the line, eliminate circuits that don't show events and follow the circuits that show the event in sharper detail. The sharper the event, the closer you are to the load causing the problem. Three phase monitoring also allows you to determine if it is a single, dual or three phase load causing the problem, further reducing the number of culprits.
To access, push the Menu button and select Transients.

Function: Inrush Currents
Inrush is the large spike most commonly caused by a motor load coming on-line. As it first energizes, the motor utilizes a higher amount of current than when runs at a constant speed. This large current draw frequently causes a large enough voltage dip to send other equipment off-line or cause the lights to blink. The Inrush function allows you to capture the inrush magnitude along with the length of time it takes the motor to come up to speed: Start recording, watch for inrush events and check the peak currents and their duration. Use the Cursor for readout of momentary values. Check if fuses, circuit breakers, and conductors in the power distribution system can withstand the inrush current during this period. If the inrush exceeds the breaker setting, it will trip. Measuring inrush current can help set appropriate breaker trip levels. Also check whether phase voltages stay stable as a large inrush can cause a voltage sag. Since the 434 Analyzer simultaneously captures inrush current and voltage trends, you can use this measurement to check voltage stability as large loads come on line.
To access, push the Menu button and select Inrush.

Function: Monitor
Monitor is a fully adjustable threshold driven feature. The Monitor screen displays a bar chart as a Go-No-Go against the thresholds. Drill down into the event to locate details for further investigation. By default, the meter is programmed to use the EN50160 power standard. These values are fully adjustable and can be set as desired. Use the Monitor function to quickly determine if a manufacturer's specification is being met for a particular load or for doing regular power audits against corporate defined limits. EN50160 is designed more for the incoming utility and not necessarily a guarantee that all loads will function within this standard.
To access, push the Monitor button.

 


 

Fluke 430 Series Frequently Asked Questions








 

Q. What is the difference between the 433 and 434 Power Quality Analyzer?
A. The 434 adds a couple features to the base 433 such as Interharmonics, Transients, Inrush currents and Energy Usage, along with greater memory storage for screen capture and datasets. The kit also includes FlukeView software and an optical communication cable to safely connect the power analyzer to your PC.  

Q. I purchased a 433 and now have need for the features of a 434. Can I upgrade?
A. YES, The 433 can be field upgraded to include all the feature of a 434. The purchase of the upgrade also includes the FlukeView software and optical communications cable. To purchase the upgrade, visit your distributor.  

Q. Click here for an overview of all the functions available in the 43X Power Quality Analyzers?  

Q. Why do many of the functions warn me about using the power adapter when I want to run off of the internal battery?
A. This warning is designed to help prevent data loss. When you select trending functions that can run over a long time period, the unit alerts you that the adapter is not plugged in, just in case you intend to record for longer than the seven hours of battery life.  

Q. USB cable driver installation issues.
A. If you encounter USB cable driver installation issues, review the READ-ME document on the CD. It contains detailed instructions along with steps for adjusting the most common problems.  

Q. What is the difference between "Dips & Swells", "Transients" and the "Monitor" function?
A. Transients require a trigger setting and then creates a graphical representation of the sinewave when that trigger is crossed. Dips & Swells does not require threshold configuration – it provides a trend chart and a text listing of changes in nominal voltages. Monitor compares incoming power to EN50160 or user defined thresholds. It then presents a go no-go chart that the user can use to drill down into the event listings.  

Q. The unit displays unusual color codes & labels. Can these be adjusted?
A. Press the Setup button, followed by F4 to access the User Preferences menu. Select Phase Identification to toggle between the L1-L2-L3 and A-B-C phase labels. Under Phase Colors, select F1 to use U.S. defaults.  

Q. Why does the unit keep turning off?
A. The 430 Series is programmed to prevent accidental power-ons that could inadvertently discharge the battery. If you don't select another function after pushing the power-on button, the unit will power-off in 15 seconds. To adjust the auto-off feature, press the Setup button, choose User Preferences and then Battery Save/Auto-OFF.  

Q: I have a power quality problem. Where do I start?
A: Start with basic real time readings of your three-phase power:

  1. Select Unbalance from the menu and see if the phases are balanced. Having more loads on one or two phases can cause a three-phase motor to overheat and fail prematurely.
  2. Select Volts/Amps/Hertz from the menu.
    • Verify that the RMS voltages are within acceptable limits. Low voltage can be just as damaging as high voltage.
    • Look for excessive neutral current. This is a common cause for overheated neutral wires and malfunctioning sensitive computer loads and can point to bad grounding or incorrect neutral to ground bonds.
 

Q: Nuisance breaker tripping.
A: Select Inrush Currents from the menu, check the startup current of the motor load, and see if exceeds the breaker rating. Startup currents are often 5 times the operating rating of the motor and are frequently overlooked. Tip: Outside of the high current events, many breakers have become more sophisticated and trip on other factors. This is especially true for three-phase switchgear. For example, many "smart" breakers" will trip on THD over a certain limit. Take a look at the harmonics to see if you're near the limit.  

Q: Transformer overheating & premature/repeat failure.
A: Harmonics are the leading cause for transformer over heating and premature failure. Harmonics also reduce the efficiency of a transformer. Select the Harmonics function from the menu to trend THD and also identify which frequencies are present on voltage, current or power. Harmonics are also a consideration when sizing the neutral conductor and why the NEC code recommends at least a double sizing. It can also be a factor in motor over heating .  

Q: My snapshots look within tolerance, but I still have a problem.
A: Many power quality problems are a result of loads turning on/off. Troubleshooting this requires longer term monitoring, as it may happen when you are not present at the panel. Having a monitor trend and capture excursions is essential. Set the 430 series Monitor function to run over a period that characterizes the problem. Tip: Keeping a log of complaints will help you determine when and how often the problem occurs – and how long to monitor for. Then, line up particular complaint times with the data captured during those same period and correlate repetitive events with equipment cycles.  

Q: What is in-rush current?
A: Inrush is the large spike most commonly caused by a motor load coming on-line. As it first energizes, the motor utilizes a higher amount of current than when runs at a constant speed. This large current draw frequently causes a large enough voltage dip to send other equipment off-line or cause the lights to blink. The Inrush function of the 434 allows you to capture the inrush magnitude along with the length of time it takes the motor to come up to speed. If the inrush magnitude and duration exceeds the breaker setting, it will trip -- even though the motor's normal current draw is much lower.  

Q: How do I locate the cause of an event?
A: To isolate the fault location, use the 434 Transients function and monitor at several points in the distribution. As you work your way down the line, eliminate circuits that don't show events and follow the circuits that show the event in sharper detail. The sharper the event, the closer you are to the load causing the problem. Three-phase monitoring also allows you to determine if it is a single, dual or three phase load causing the problem, further reducing the number of culprits.  

Q. Why would I use the less expensive 430 Series power quality analyzer to do a power quality study, rather than a traditional power quality monitor or recorder? Isn't expensive better?
A. Just like any job, having the right tool is what matters most. The 430 series is designed for front line power quality troubleshooting and audits. It's lightweight, handheld, battery operated and has the three phase capabilities required for industrial and commercial environments. It's also CAT IV rated for use at the service entrance where most audits begin. When you need to take measurements at several points along the distribution, ease of use and portability are more important than high transient capture and extensive storage. Likewise, when troubleshooting a mysterious power quality problem, you need to measure dips, swells, harmonics, unbalance, power, flicker and waveforms before you know what setups and thresholds to set. The 430 Series can begin measuring immediately, while a monitor or recorder requires thresholds. Then, once more complexity is required, the 430 series can become a threshold driven meter for pass/fail reporting. It can also capture and characterize inrush current, store and transfer data to a PC for later analysis and report generation, and capture transients at 5uS.

 

Phone: 813-971-5001
Fax : 813-971-5117

Omni Controls Inc.
5309 Technology Dr.
Tampa, FL 33647

Toll Free
1-800-783-6664

email sales@omnicontrols.com
Sales@Omnicontrols.com

We guarantee a 24 hour response on all inquiries made via email.
For quicker response please call Omni Controls
at any of the above numbers

 


Please Note: All prices subject to change without notice
copyright©omnicontrols.com - All Rights Reserved.
Terms and Conditions for Omni Controls Inc - online.
Legal Disclaimer
Supplementary Information and Cover Art Copyright omnicontrols.com. All rights reserved.

copyright © omnicontrols 2005
Omni Controls Inc.
5309 Technology Dr.
Tampa, FL 33647

Email: sales@omnicontrols.com

Phone: 800-783-6664
Fax: 813-971-5117