10kV Insulation Resistance Tester Kit with Hard Carrying Case and Certificate of Calibration
New Page 1
Digital insulation
testing up to 10kV
The new 1555 and
redesigned Fluke 1550C insulation resistance testers, offer digital insulation
testing up to 10kV, making them ideal for testing a wide range of high voltage
equipment including switchgear, motors, generators and cables. Fluke insulation
testers can now conduct the entire range of test voltages specified in IEEE
43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating.
With measurement storage and PC interface, the 1555 and 1550C are perfect tools
for preventative or predictive maintenance programs designed to identify
potential equipment failures before they occur.
| Model
name |
Description |
| FLUKE-1555/Kit |
10 KV INSULATION TESTER KIT |
| TL1550EXT |
TL1550EXT, 25 Foot Extended Test Lead Set |
| FLUKE-1555 |
10 KV INSULATION TESTER |
| FLUKE-1550C/Kit |
5 KV INSULATION TESTER KIT |
| FLUKE-1550C |
5 KV INSULATION TESTER |
Features and benefits:
- Test voltages up to 10 kV provides solutions
for all applications
- CAT III 1000 V, CAT IV 600 V safety rating
- Voltage breakdown detection alerts the user
that voltage is present and gives the voltage reading up to 600 V ac or dc
for increased user safety
- Selectable test voltages in 50 V steps from
250 to 1000 V, and 100 V steps above 1000 V
- Measurements can be stored in up to 99 memory
locations, with each location assigned a unique, user defined, label for
easy recall
- Long battery life gives the user over 750
tests between charges
- Automatic calculation of Dielectric Absorption
(DAR) and Polarization Index (PI) with no additional setup
- Guard system eliminates the effect of surface
leakage current on high-resistance measurements
- Large digital/analog LCD for easy viewing
- Capacitance and leakage current measurement
- Ramp function for breakdown testing
- Resistance measurements up to 2TΩ
- Timer settings up to 99 minutes for timed
tests
- 3-year warranty
Electrical
specifications
The tester’s
accuracy is specified for one year after calibration at operating temperatures
of 0 °C to 35 °C. For operating temperatures outside the range (-20 °C to 0
°C and 35 °C to 50 °C), add ± .25 % per °C, except on the 20 % bands add ±
1 % per °C.
| Insulation
resistance measurement |
| Test
voltage (dc) |
Range
(dc) |
Accuracy
(± reading) |
| 250 V |
< 200 kΩ
200 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ |
unspecified
5 %
20 %
unspecified |
| 500 V |
< 200 kΩ
200 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ |
unspecified
5 %
20 %
unspecified |
| 1000 V |
< 200 kΩ
200 kΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ |
unspecified
5 %
20 %
unspecified |
| 2500 V |
< 200 kΩ
200 kΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ |
unspecified
5 %
20 %
unspecified |
| 5000 V |
< 200 kΩ
200 kΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ |
unspecified
5 %
20 %
unspecified |
| 10000 V |
< 200 kΩ
200 kΩ to 200 GΩ
10 GΩ to 2 TΩ
> 2 TΩ |
unspecified
5 %
20 %
unspecified |
| Bar
graph range |
0
to 1 TΩ |
| Insulation
test voltage accuracy |
|
-0 %, +10 % at 1 mA load current |
|
| Induced ac
mains current rejection |
|
| Charging
rate for capacitive load |
|
| Discharge
rate for capacitive load |
|
| |
Range |
Accuracy |
| Leakage
current measurement |
1 nA to 2 mA |
± (5 % + 2 nA) |
| Capacitance
measurement |
0.01 uF to
15.00 μF |
± (15 % rdg + 0.03
μF) |
| Timer |
0 to 99
minutes |
| Resolution |
Setting: 1 minute
Indication: 1 second |
|
| Live
circuit warning |
| Warning range |
| 30 V to 660 V ac/dc, 50/60 Hz |
|
| Voltage accuracy |
| ± (15 % + 2 V) |
|
| General
specifications |
| Display |
75
mm x 105 mm |
| Power |
|
12 V lead-acid rechargeable
battery, Yuasa NP2.8-12 |
|
| Charger
Input (AC) |
|
| This
Class II (double insulated) instrument is supplied with a Class 1
(grounded) power cord. The protective earth terminal (ground pin) is not
connected internally. The extra pin is for added plug retention only. |
| Dimensions |
|
170 mm x 242 mm x 330 mm (6.7 in x
9.5 in x 13 in) |
|
| Weight |
|
| Temperature
(operating) |
|
-20 ºC to 50 ºC (-4 ºF to 122
ºF) |
|
| Temperature
(storage) |
|
-20 ºC to 65 ºC (-4 ºF to 149
ºF) |
|
| Humidity |
|
80 % to 31 ºC decreasing linearly
to 50 % at 50 ºC |
|
| Altitude |
|
| Enclosure
sealing |
|
| Input
overload protection |
|
| Electromagnetic
compatibility |
|
| Certifications |
|
| Safety
compliance |
|
CAT III 1000 V, CAT IV 600 V |
|
| Polution
degree |
|