2, 4, 6 or 12 direct universal inputs: DC voltage, current and
thermocouples
High speed storage capability: up to 8 samples per second per
channel.
Multiple storage media options: 3 1/2" 1.44MB disk,or
Compact Flash up to 64MB.
5.6" Brilliant TFT active matrix color display or 5"
monochrome display.
Intuitive Touchscreen
Control with anti-glare coating.
IP65 rated front panel.
Standard DIN enclosure: 144mm x 144mm bezel
6 relay contact or solid state relay outputs/3 digital control
input.
Parallel printer output.
Serial output
options: RS232 or RS485.
10BaseT Ethernet connection.
Companion Software for unit configuration, communication, data analysis,
print and export to standard spreadsheet/database applications.
Overview
The Data-Chart 2000 has 2, 4, 6 or 12 direct universal isolated inputs that are
menu selectable for DC voltage, DC current and thermocouples. The intuitive
Touchscreen control provides easy, fast set up and operation.
Display
Our brilliant 5.6" (142mm) active matrix TFT color display is the largest
in it’s class and with a special anti-glare coated Touchscreen the
viewability is second to none. If you need a more economical solution, the
DC2000 can also be ordered with a super bright blue monochromatic display.
Recording
Data is stored in non-volatile internal RAM and downloaded to removable media
automatically on a preset basis or on demand. Standard removable storage is a
3.5" 1.44Mb disk or, for large amounts of data, you can choose the PCMCIA
card drive option which will store up to 200 Mb of Data!
Speed
A measurement rate of 8 samples per second for 1 channel makes the DC2000 ideal
for recording process signals that change quickly such as pressure. Or, if you
require information less frequently, you can select to record between 8 samples
per second and ten minutes.
Communications
Communication options offer great flexibility in accessing data or controlling
the DC2000. Data can be accessed and downloaded over standard phone line using
the RS232C option and a modem. The RS485 MODBUS option will allow the DC2000 to
be installed into an existing MODBUS network or you can connect up to thirty one
recorders in series. The 10BaseT Ethernet port option allows direct connection
to LAN’s or WAN’s and the standard TCP/IP protocol means that you can
transfer data over the Internet.
There are more than 20 display modes to choose from. This gives you
unparalleled flexibility to view only the data you need to see in virtually any
format. Grouping of channels maximizes efficiency.
Display Type Color CCFL
backlit Active Matrix TFT Liquid Crystal Display (5.6 inch) with
touchscreen control. Resolution
320 x 240 pixels. Display Type Mono CCFL
backlit STN Liquid Crystal Display (5.0 inch) with touchscreen
control. Resolution
240 x 128 pixels. Display Modes
Graphics (Trending vertical or horizontal), Bar Graphs (vertical
or horizontal), Digital Meters, Alphanumeric Alarm and Event
Data or combinations on a split
screen. Review trended data. Search by time, date or signal
value. Virtual Chart Speed
Programmable from 0.5in/hr to 600in/hr or 10mm.hr to
15,000mm/hr. Chart speed is independent of storage rate. Display Windows Time/Date,
Graphics (Bars, Large Digital, Trends), Disk Status, Systems
Status, Menu Button Bar, Unit Indentification,Alarms/Events.
Touch Screen
Touch sensitive screen with Button Bar for simple programming
and easy operation. Math Package Algebraic equations (basic math,
powers, roots, natural and base 10 logarithms, exponentiation),
peak monitoring, differentials, true rolling averages, time
averages, gated timing, conditionals (Boolean logic),
totalization, logarithmic scaling. 12 Programmable constants. Buffer Internal 128k buffer (RAM) enables
real time browsing of historic chart data independent of
recorded data. Equivalent browse capability is approximately 560
pen inches. This represents about 5½ days for 4 pens at 1
inch/hour.
File Browse Any data file on disk can be
browsed. File directory allows selection of different file
names. Disk Full Alarm User can set disk full
threshold. Disk errors and alarms can be routed to contact
closure. Trend direction User selectable Horizontal or
Vertical chart trending. "Pen" pointers for easy trace
identification.
Power Requirements
100 to 240Vac, 50/60Hz or 125 to 300Vdc, 35VA max. Optional
24Vdc +/-15%. Power Fail Protection
Programmed parameters stored in non-volatile memory. Clock
battery backed. Data retention time without power >12
months.Chart and alarm browse buffers stored in non-volatile
memory. Safety
UL (3111-1) cUL (IEC1010-1) CE low voltage directive 73/23/EEC.
Complies with EN 61010-1.
Temperature 5°C
to 40°C per UL3111-1/IEC1010-1 with disk drive. -10°C to 50°C
with PCMCA drive or ZIPTM Drive.
Humidity 10% to 80% RH
per UL3111-1/IEC1010-1. Wash Down
IP65 Front panel only.
Alarm Contacts 3
or 6 isolated Form C, 3 amp @ 250Vac or 26 Vdc.
Solid State Relays 3 or 6, 0.5 amp @ 30Vdc.
Remote Inputs 3 isolated
inputs, user selectable as dry contact or 5 to 12 Vdc (mech.
relay), 12 to 24 Vdc (SS relay) activated.. Inputs share
a common. Configurable for chart control, alarm
acknowledge/reset, event markers, totalizer reset or logic
input.
Communications ESD
protected RS232 with full hand shaking. Supports modem or
isolated RS485 port. Protocol:
MODBUS RTU, MODBUS ASCII or serial printer port. Ethernet:
10BaseT. Unit may be remotely configured.
Printer Port Parallel
printer port (25 pin D shell connector).
Companion Software is
a powerful and intuitive Windows based application program that allows
you to monitor real time data or review previously recorded data in
graphic or tabular format, search files for specific events, link
alarm and event files to trended data, print graphic or tabular files
and export files to spreadsheet applications such as Lotus 1-2-3 or
Excel. Recorder configurations are easily generated using Companion
Software and can be downloaded to diskette or PCMCIA card and
transferred to the recorder or transferred directly over RS232 or RS485
serial line.
Monitor, configure and control up to 31
units with the RS485 MODBUS option or control from remote
locations with the RS232 modem control. Whatever the application,
Companion Software puts you in complete control.
Features
Display files in graphic
format.
Use the cursor to pin point
exact values with time and data information.
Search data by signal values
or date/time.
Each point is displayed with
its corresponding tag name, engineering and scale units.
Compress graphic files in
time.
Zoom in on areas of key
interest.
Display data in tabular
format with time and date information for each sample.
Transfer data over R5232 or
RS485 serial line.
Network up to 31 Data-Chart
3000's on one RS485 serial link.
Transfer data from remote
sites using direct dial modem capability.
Display Alarm/Event
information.
The time and type of each
alarm is displayed.
Information as to when an
alarm condition returns to normal is also displayed.
Alarm/Event files and
graphic files can be tiled together on one screen and
time synchronized.
Create recorder
configurations using Companion and transfer via serial
line, 3.5 in disk, or PCMCIA card.
Export files to spreadsheet
applications such as Excel, Lotus 1-2-3 etc
Made in the USA
Phone:
813-971-5001
Fax : 813-971-5117
Omni
Controls Inc.
5309 Technology Dr.
Tampa, FL 33647
Toll
Free
1-800-783-6664
Sales@Omnicontrols.com
We
guarantee a 24 hour response on all inquiries made via email.
For quicker response please call Omni Controls
at any of the above numbers