- Air Conditioning
Setra - Heating, Ventilation, Air Conditioning and Refrigeration
Model 264/C264 Low
Differential Pressure
Price - $195.00
Features
- HVAC & VAV Control
- Energy Management Systems
- OEM
- Environmental Pollution Control
- Oven Pressurization & Furnace
- Draft Control
- Lab and Fume Hood Control
- Medical Instrumentation
|

|
SPECIFICATIONS:
| Model
264/C264 Specifications |
| Full Scale Pressure Output |
Model 264 (Voltage):
Unidirectional:
5 VDC nominal
Bi-directional:
5 VDC nominal |
Model C264 (Current):
Unidirectional:
20 mA |
| Zero Pressure Output |
Unidirectional:
0 VDC
Bi-directional:
2.5 VDC |
Unidirectional:
4 mA
Bi-directional:
12 mA |
Accuracy
(RSS Method) |
±1.0% FS (±0.4% FS & ±0.25% FS optional) |
| Type of Pressure |
Very Low Differential |
| Pressure Ranges |
- Unidirectional:
- 0 to 0.1, 0.25, 0.5, 1, 2.5, 5, 10, 25 in. WC
- Bi-directional:
- 0 to ±0.1, ±0.25, ±0.5, ±1, ±2.5, ± 5 in. WC
|
| Thermal Effects |
- Compensated Range °F (°C):
- 40 to 100 (5 to 38)
- %FS/100°F(100°C)max.zero/span:
- ±3.3 (±6.0) zero and span combined
|
| Media |
Typically air or similar non-conducting gases |
|
Model 265 Low
Differential Pressure
Price - $150.00
Features
- HVAC Equipment
- Energy Management
- Variable Air Volume (VAV)
- Environmental Pollution Control
- Static Duct & Clean Room Pressures
- Oven Pressurization & Furnace Draft Controls
- Medical Instrumentation
|

|
SPECIFICATIONS:
| Model
265 Specifications |
| Electrical Output Voltage |
0 to 5 VDC |
| Bidirectional Output (Voltage) at Zero |
2.5 VDC |
| Electrical Output Current |
4 to 20 mA |
Accuracy
(RSS Method) |
±1.0% FS
(Optional Accuracies: ±0.4%, ±0.25%, ±0.5% FS) |
| Type of Pressure |
Very Low Differential Pressure |
| Pressure Ranges |
Unidirectional:
0 to 0.25, 0.5, 1.0, 2.5, 5.0, 10, 25, 50, 100 in.WC
Bidirectional:
0 to ±0.1, ±0.25, ±0.5, ±1.0, ±2.5, ±5.0, ±10, ±25, ±50 in.WC |
| Thermal Effects |
- Thermal Compensation °F (°C):
- 0 to +150 (-18 to +65)
- Zero/Span Shift %FS/°F (°C):
- 0.033 (0.06)
|
| Media |
Typically air or similar non-conducting gases |
|
Model 267 Low
Differential Pressure
Price - $215.00
Features
- HVAC & VAV Control
- Variable Air Volume & Fan Control
- OEM
- Energy Management Systems
- Environmental Pollution Control
- Oven Pressurization & Furnace
- Draft Control
- Lab and Fume Hood Control
- Medical Instrumentation
|

|
SPECIFICATIONS:
| Model
267 Specifications |
| Electrical Output, Voltage |
0 to 5 VDC
0 to 10 VDC |
| Bidirectional Voltage Output at Zero |
Mid-range of specified output |
| Electrical Output, Current |
4 to 20 mA |
| Bidirectional Current Output at Zero |
12 mA |
Accuracy
(RSS Method) |
±1.0% FS (±0.4% FS & ±0.25% FS optional) |
| Type of Pressure |
Very Low Differential |
| Pressure Ranges |
- Unidirectional:
- 0 to 0.1, 0.25, 0.5, 1, 2.5, 5, 10 in.WC
- 0 to 2.5, 5, 10, 25, 50, 100, 250 mmWC
- 0 to 0.25, 0.5, 1, 2.5, 5, 10, 25 mbar
- 0 to 25, 50, 100, 250, 500, 1000, 2500 Pa
- Bi-directional:
- 0 to ±0.1, ±0.25, ±0.5, ±1, ±2.5,± 5 in.WC
- 0 to ±2.5, ±5, ±10, ±25, ±50, ±100, mmWC
- 0 to ±0.25, ±0.5, ±1, ±2.5, ±5, ±10 mbar
- 0 to ±25, ±50, ±100, ±250, ±500, ±1000 Pa
|
| Thermal Effects |
- Compensated Range °F (°C):
- 40 to 149 (5 to 65)
- %FS/100°F(100°C)max.zero/span:
- ±3.3 (±6.0) zero and span combined
|
| Media |
Typically air or similar non-conducting gases |
| Option |
LCD Display |
|
Model 267MR
Price - $225.00
Features
- HVAC & VAV Control
- Variable Air Volume & Fan Control
- OEM
- Energy Management Systems
- Environmental Pollution Control
- Oven Pressurization & Furnace
- Draft Control
- Lab and Fume Hood Control
- Medical Instrumentation
|

|
SPECIFICATIONS:
| Model
267MR Specifications |
| Electrical Output, Voltage (Field Selectable) |
0 to10 VDC
0 to 5 VDC |
| Bidirectional Voltage Output at Zero |
Mid-range of specified output |
| Electrical Output, Current |
4 to 20 mA |
| Bidirectional Current Output at Zero |
12 mA |
Accuracy
(RSS Method) |
±1.0% FS |
| Type of Pressure |
Differential |
| Pressure Ranges |
in. W.C.
MR1 = 0 to 0.1, ±0.05
MR2 = 0 to 0.25, 0.5, 1, ±0.125, ±0.25, ±0.5
MR3 = 0 to 1.25, 2.5, 5.0, ±0.625, ±1.25, ±2.5
MR4 = 0 to 7.5, 15, 30, ±3.75, ±7.5, ±15
Pascals
MR5 = 0 to 25, 12.5
MR6 = 0 to 50, 100, 200, ±25, ±50, ±100
MR7 = 0 to 250, 500, 1000, ±125, ±250, ±500
MR8 = 0 to 625, 1250, 2500, ±312, ±625, ±1250
MR9 = 0 to 1875, 3750, 7500, ±937, ±1875, ±3750 |
| Thermal Effects |
- Compensated Range °F (°C):
- 40 to 149 (5 to 65)
- %FS/100°F(100°C)max.zero/span:
- ±3.3 (±6.0) zero and span combined
|
| Media |
Typically air or similar non-conducting gases |
|
|