- Air Conditioning
Setra - Heating, Ventilation, Air Conditioning and Refrigeration

Model 264/C264 Low Differential Pressure

Price - $195.00

Features

  • HVAC & VAV Control
  • Energy Management Systems
  • OEM
  • Environmental Pollution Control
  • Oven Pressurization & Furnace
  • Draft Control
  • Lab and Fume Hood Control
  • Medical Instrumentation

SPECIFICATIONS:
Model 264/C264 Specifications
Full Scale Pressure Output Model 264 (Voltage):
Unidirectional:
5 VDC nominal
Bi-directional:
5 VDC nominal
Model C264 (Current):
Unidirectional:
20 mA
Zero Pressure Output Unidirectional:
0 VDC
Bi-directional:
2.5 VDC
Unidirectional:
4 mA
Bi-directional:
12 mA
Accuracy
(RSS Method)
±1.0% FS (±0.4% FS & ±0.25% FS optional)
Type of Pressure Very Low Differential
Pressure Ranges
Unidirectional:
0 to 0.1, 0.25, 0.5, 1, 2.5, 5, 10, 25 in. WC
Bi-directional:
0 to ±0.1, ±0.25, ±0.5, ±1, ±2.5, ± 5 in. WC
Thermal Effects
Compensated Range °F (°C):
40 to 100 (5 to 38)
%FS/100°F(100°C)max.zero/span:
±3.3 (±6.0) zero and span combined
Media Typically air or similar non-conducting gases

 


 

Model 265 Low Differential Pressure

Price - $150.00

Features

  • HVAC Equipment
  • Energy Management
  • Variable Air Volume (VAV)
  • Environmental Pollution Control
  • Static Duct & Clean Room Pressures
  • Oven Pressurization & Furnace Draft Controls
  • Medical Instrumentation

SPECIFICATIONS:
Model 265 Specifications
Electrical Output Voltage

0 to 5 VDC

Bidirectional Output (Voltage) at Zero 2.5 VDC
Electrical Output Current

4 to 20 mA

Accuracy
(RSS Method)

±1.0% FS
(Optional Accuracies: ±0.4%, ±0.25%, ±0.5% FS)

Type of Pressure Very Low Differential Pressure
Pressure Ranges Unidirectional:
0 to 0.25, 0.5, 1.0, 2.5, 5.0, 10, 25, 50, 100 in.WC
Bidirectional:
0 to ±0.1, ±0.25, ±0.5, ±1.0, ±2.5, ±5.0, ±10, ±25, ±50 in.WC
Thermal Effects
Thermal Compensation °F (°C):
0 to +150 (-18 to +65)
Zero/Span Shift %FS/°F (°C):
0.033 (0.06)
Media Typically air or similar non-conducting gases

 

Model 267 Low Differential Pressure

Price - $215.00

Features

  • HVAC & VAV Control
  • Variable Air Volume & Fan Control
  • OEM
  • Energy Management Systems
  • Environmental Pollution Control
  • Oven Pressurization & Furnace
  • Draft Control
  • Lab and Fume Hood Control
  • Medical Instrumentation

SPECIFICATIONS:
Model 267 Specifications
Electrical Output, Voltage

0 to 5 VDC
0 to 10 VDC

Bidirectional Voltage Output at Zero Mid-range of specified output
Electrical Output, Current

4 to 20 mA

Bidirectional Current Output at Zero 12 mA
Accuracy
(RSS Method)
±1.0% FS (±0.4% FS & ±0.25% FS optional)
Type of Pressure Very Low Differential
Pressure Ranges

 

Unidirectional:
0 to 0.1, 0.25, 0.5, 1, 2.5, 5, 10 in.WC
0 to 2.5, 5, 10, 25, 50, 100, 250 mmWC
0 to 0.25, 0.5, 1, 2.5, 5, 10, 25 mbar
0 to 25, 50, 100, 250, 500, 1000, 2500 Pa
Bi-directional:
0 to ±0.1, ±0.25, ±0.5, ±1, ±2.5,± 5 in.WC
0 to ±2.5, ±5, ±10, ±25, ±50, ±100, mmWC
0 to ±0.25, ±0.5, ±1, ±2.5, ±5, ±10 mbar
0 to ±25, ±50, ±100, ±250, ±500, ±1000 Pa
Thermal Effects
Compensated Range °F (°C):
40 to 149 (5 to 65)
%FS/100°F(100°C)max.zero/span:
±3.3 (±6.0) zero and span combined
Media Typically air or similar non-conducting gases
Option LCD Display

 


 

Model 267MR

Price - $225.00

Features

  • HVAC & VAV Control
  • Variable Air Volume & Fan Control
  • OEM
  • Energy Management Systems
  • Environmental Pollution Control
  • Oven Pressurization & Furnace
  • Draft Control
  • Lab and Fume Hood Control
  • Medical Instrumentation

SPECIFICATIONS:
Model 267MR Specifications
Electrical Output, Voltage (Field Selectable)

0 to10 VDC
0 to 5 VDC

Bidirectional Voltage Output at Zero Mid-range of specified output
Electrical Output, Current

4 to 20 mA

Bidirectional Current Output at Zero 12 mA
Accuracy
(RSS Method)
±1.0% FS
Type of Pressure Differential
Pressure Ranges in. W.C.
MR1 = 0 to 0.1, ±0.05
MR2 = 0 to 0.25, 0.5, 1, ±0.125, ±0.25, ±0.5
MR3 = 0 to 1.25, 2.5, 5.0, ±0.625, ±1.25, ±2.5
MR4 = 0 to 7.5, 15, 30, ±3.75, ±7.5, ±15

Pascals
MR5 = 0 to 25, 12.5
MR6 = 0 to 50, 100, 200, ±25, ±50, ±100
MR7 = 0 to 250, 500, 1000, ±125, ±250, ±500
MR8 = 0 to 625, 1250, 2500, ±312, ±625, ±1250
MR9 = 0 to 1875, 3750, 7500, ±937, ±1875, ±3750
Thermal Effects
Compensated Range °F (°C):
40 to 149 (5 to 65)
%FS/100°F(100°C)max.zero/span:
±3.3 (±6.0) zero and span combined
Media Typically air or similar non-conducting gases

 


Phone: 813-971-5001
Fax : 813-971-5117

Omni Controls Inc.
5309 Technology Dr.
Tampa, FL 33647

Toll Free
1-800-783-6664

email sales@omnicontrols.com
Sales@Omnicontrols.com

We guarantee a 24 hour response on all inquiries made via email.
For quicker response please call Omni Controls
at any of the above numbers

 


Please Note: All prices subject to change without notice
copyright©omnicontrols.com - All Rights Reserved.
Terms and Conditions for Omni Controls Inc - online.
Legal Disclaimer
Supplementary Information and Cover Art Copyright omnicontrols.com. All rights reserved.

copyright © omnicontrols 2005
Omni Controls Inc.
5309 Technology Dr.
Tampa, FL 33647

Email: sales@omnicontrols.com

Phone: 800-783-6664
Fax: 813-971-5117