A capture hood (flow measuring hood) is an instrument used to measure volumetric air flows from supply or exhaust diffusers and grilles. Capture hoods make fast, repeatable measurements. There are several models and hood sizes available to meet the wide variety of user needs. Choose from the following Alnor balometer and manometers: |
Accessories for Electronic Balometer
The Electronic Balometer Capture Hood uses thermal anemometry to measure volumetric flow. This hood model is popular with contractors and facilities personnel because of its versatility, lightweight construction, and ability to document and store readings. A sturdy middle handle allows you to comfortably hold the Balometer hood with one hand. The removable digital meter can be used with optional accessory probes to measure velocity, temperature, and relative humidity.
|
Electronic
Balometer
|
|
| range | 50-2000 cfm (85-3400 m3/hr, 24-945 l/s) |
| accuracy | supply: ±(3% of reading + 7 cfm) (±3%
of reading + 12 m3/hr), (±3% of reading + 3.3 l/s) exhaust: ±(4% of reading + 7 cfm) (±4% of reading + 12 m3/hr), (±4% of reading + 3.3 l/s) |
| measurement units | cfm, m3/h, l/s |
| display | digital display |
| instrument weight | 8.7 lb (4 kg) with 2 ft x 2 ft (610 mm x 610 mm) hood attached |
| batteries | three AA-size alkaline |
| battery life | minimum 10 hours continuous use |
| hood sizes | APM 151: 2 ft x 2 ft (610 mm x 610 mm) APM 153: same as APM 151 plus 2 ft x 4 ft (610 mm x 1220 mm) and 1 ft x 4 ft (305 mm x 1220 mm) APM 155: same as APM 153 plus 3 ft x 3 ft (915 mm x 915 mm) and 1 ft x 5 ft (305 mm x 1525 mm) |
|
Model
275/175
|
Model
220B
|
||
| range | velocity | 20-6000 fpm (0.1-30 m/s) | NA |
| temperature | 32-122°F (0-50°C) | 32-140°F (0-60°C) | |
| humidity | NA | 0-100% RH | |
| accuracy | velocity | ±5 fpm, 20-100 fpm (±0.025 m/s), 0.1-0.5
m/s ±(3% of reading + 2 fpm), 101-700 fpm (±3% of reading + 0.01 m/s), 0.5 m/s-3.56 m/s ±(3% of reading + 20 fpm), 701-4000 fpm (±3% of reading + 0.1 m/s), 3.56 m/S-20.32 m/s ±(3% of reading + 200 fpm), 4001-6000 fpm (±3% of reading + 1.02 m/s), 20.33 m/s-30.48 m/s |
NA |
| temperature | ±(0.5% of reading + 1°F [1°C]) | ±(0.4% of reading + 1°F [1°C]) | |
| humidity | NA | ±2% RH, 10-96% RH at 77°F (25°C) | |
| probe dimensions | 45-inch (114-cm) telescopic (275), 12-inch (30-cm) straight (175) |
10-inch (25-cm) straight, 0.9-inch (2.2-cm) diameter |
|
|
Model 8928
|
||
| printing method | Thermal serial dot matrix | |
| printing speed | Approximately 0.8 lines/sec | |
| external dimensions | 5.3 in. x 5.1 in. x 2.5 in. | |
| weight | Approximately 14 oz | |
| temperature range | 32°F to 122°F | |
| humidity range | 30% RH to 80%RH | |
| printer interface | type | serial |
| baud rate | 1200,2400,4800,9600 | |
Air
Volume Instruments (Balometers) Selection Guide
|
|
LoFlo Balometer
|
Balometer JR.
|
Standard Balometer
|
EBT |
||||
|
|
||||||||
| 10-500 CFM (17-850
m3/hr) |
·
|
·
|
|
|
|
|
|
|
| 0-1400 CFM (0-2400
m3/hr) |
|
|
·
|
·
|
|
|
|
|
| 0-2000 CFM (0-3400
m3/hr) |
|
|
|
|
·
|
·
|
|
|
| 25-2500 CFM (42-4250
m3/hr) |
|
|
|
|
|
|
|
·
|
| Temperature (°F or °C) |
|
|
|
|
|
|
|
·
|
| Velocity, temperature or %RH probe |
|
|
|
|
|
|
|
·
|
| With 2' x 2' hood |
·
|
|
·
|
|
·
|
|
|
|
| With 2' x 2', 2' x 4',
1' x 4' hoods |
|
|
|
|
|
·
|
|
·
|
| With 2'x 2', 2' x 4',
1' x 4', 1' x 5', and 3' x 3' hoods |
|
|
|
|
|
|
·
|
·
|
| 16" x 16"
hood |
|
·
|
|
·
|
·
|
·
|
·
|
|
| Deflecting vane
anemometer (analog display) |
|
|
·
|
·
|
·
|
·
|
·
|
|
| Pressure Sensor
(manometer) |
|
|
|
|
|
|
|
·
|
| Thermo-anemometer sensor |
·
|
·
|
|
|
|
|
|
|
| Inherently
intrinsically safe |
|
|
·
|
·
|
·
|
·
|
·
|
|
| Statistics (min., max.,
and avg.) |
|
|
|
|
|
|
|
·
|
| Data log (recall /
download to a PC) |
|
|
|
|
|
|
|
·
|
| K-factor input or field
calibration |
·
|
·
|
|
|
|
|
|
·
|
| Tilt and Backlit LCD Display |
|
|
|
|
|
|
|
·
|
| Automatic Density Correction |
|
|
|
|
|
|
|
·
|
| Backpressure Compensation |
|
|
|
|
|
|
|
·
|
| Internal NiMH Battery Charging |
|
|
|
|
|
|
|
·
|
CO2 METERS |
FLOW |
HYGROMETERS |
|