-1000 to +3500 and
-10000 to +35000 Count Resolution
Thermocouple, RTD, and
Thermistor
Temperature Measurement
in °C or °F without Recalibration
VDC and mADC Process
Measurement
Large, Easy-to-Read LED
Display
High Noise Rejection
Rugged Construction
Plug-in Range Modules
and Options
Made in USA
460 Series
Selectable
for Thermocouple, RTD, and Thermistor Functions
Laboratory
Accuracy
Full Range
0.1° Resolutions with Thermocouples and RTD; 0.01° with
Thermistors
Up to 24
Input Points and 28 Sensor Input Types
Easy
One-Stroke Calibration of All Input Ranges
Minimum,
Maximum, Average, and Rate of Change Monitoring
Digital
Outputs, Alarm, Analog Output, Enhancement Options
Made In USA
Digital
Temperature Measurement
The Series 460
measures and displays accurate temperatures reliably and repeatedly.
Sensor input types are selectable from a smooth, environmentally
protected front panel keypad. Choose either Model 460, a 4-digit
resolution meter, or Model 461, a higher resolution 5-digit instrument.
With either model, you can add a variety of input options to tailor the
instrument precisely to your needs.
For unmatched
repeatability and accuracy, the Series 460 uses a new wide-range,
integrating voltage-to-frequency conversion technique. An integral
microprocessor generates periodic digital auto-zero readings for
baseline verification.
Because
temperature sensors emit very low signal levels, RFI and EMI often
present the most serious obstacle to accurate readings. The Series 460
common mode rejection ratio exceeds 120dB, ensuring rejection of
unwanted common mode voltages from ground loops that would otherwise
make measurements unreliable. Outputs are also shielded, preserving data
integrity all the way to your readout or printout.
Range Accuracy and Inputs
Range Designator
on Display
Sensor Type
Range
Accuracy
(all ±)
Thermocouple
J T/C
Iron-Constantan
-336 to 2193°F
-204 to 1200°C
68 to 1473 K
0.5°F
0.3°C
0.3 K
K T/C
Chromel®*-Alumel®*
-229 to 2503°F
-184 to 1373°C
88 to 1646 K
0.6°F
0.3°C
0.3 K
T T/C
Copper-Constantan
-373 to 753°F
-225 to 400°C
48 to 674 K
0.4°F
0.2°C
0.2 K
E T/C
Chromel®*-Constantan
-358 to 1835°F
-217 to 1001°C
56 to 1275 K
0.6°F
0.3°C
0.3 K
R T/C
Platinum-Platinum
13% Rhodium
32 to 3219°F
0 to 1770°C
273 to 2043K
1.2°F
(>79.0°F)
0.7°C
(>26.0°C)
0.7 K
(>299.2 K)
S T/C
Platinum-Platinum
10% Rhodium
32 to 3216°F
0 to 1769°C
273 to 2042 K
1.2°F
(>79.0°F)
0.7°C
(>26.0°C)
0.7 K
(>299.0 K)
B T/C
Platinum 30% Rhodium
Platinum 6% Rhodium
899 to 3309°F
481 to 1820°C
755 to 2094K
2.0°F
1.1°C
1.1 K
N T/C
Nicrosil-Nisil
32 to 2301°F
0 to 1260°C
273 to 1534 K
0.5°F
0.3°C
0.3 K
C T/C
Tungsten 5% Rhenium
Tungsten 26% Rhenium
-10 to 4200°F
-23 to 2315°C
249 to 2589 K
1.1°F
0.6°C
0.6 K
G T/C
Tungsten-Tungsten
26% Rhenium
295 to 4206°F
146 to 2318°C
419 to 2592 K
1.1°F
0.6°C
0.6 K
D T/C
Tungsten 3% Rhodium
Tungsten 25% Rhodium
-8.4 to 4203°F
-22.4 to 2317°C
250 to 2590 K
1.1°F
0.6°C
0.6 K
CGI T/C
Chromel®*-Gold
.07% Atomic Iron
-460 to 44°F
-273 to 7°C
0 to 280 K
0.4°F
0.2°C
0.2 K
FeCon
Iron Constantan
DIN
-330 to 1654°F
-210 to 901°C
71 to 1174 K
0.9°F
0.5°C
0.5 K
CuCon
Copper-Constantan
DIN
-331 to 1114°F
-201 to 601°C
71 to 874 K
0.9°F
0.5°C
0.5 K
*CHROMEL®
and ALUMEL® are
registered trademarks of the Hoskins Manufacturing Company.
RTD
PT1000 385
Platinum-100 at 0°C
3- or 4-wire
a=0.00385/DIN 43670 curve
-332 to 1571°F
-202 to 855°C
70 to 1128 K
0.2°F
0.1°C
0.1 K
PT100 392
Platinum-100 at 0°C
3 or 4-wire
a=0.00392
-410 to 1572°F
-240 to 855°C
32 to 1128 K
0.2°F
0.1°C
0.1 K
PT200 392
Platinum-200 at 0°C
3 or 4-wire
a=0.00392
-330 to 1566°F
-201 to 852°C
72 to 1125 K
0.2°F
0.1°C
0.1 K
PT1000
Platinum-100 at 0°C
3- or 4-wire
a=0.00375/HYCAL
Ultra 7 curve
-330 to 1025°F
-204 to 1200°C
68 to 1473 K
0.2°F
0.1°C
0.1 K
Cu10
Copper-10 at 25°C
3 or 4-wire
per Minco table 16-9
-337 to 507°F
-205 to 264°C
68 to 537 K
0.8°F
0.4°C
0.4 K
Ni120
Nickel-120 at 0°C
3 or 4-wire
per Minco table 7-120
-112 to 608°F
-80 to 320°C
192 to 593 K
0.4°F
0.2°C
0.2 K
Thermistor
YSI 400
Thermistor Series
YSI 400
2-wire
-42.4 to 221.7°F
-41.3 to 185.4°C
231.9 to 458.6 K
0.4°F
0.2°C
0.2 K
YSI 700
Thermistor Series
YSI 700
3-wire
31.0 to 213.0°F
-0.6 to 100.6°C
272.6 to 373.8 K
0.4°F
0.2°C
0.2 K
Series 460 Options
Tailor
the instruments with options to extend your measurement capabilities.
Five option slots are available in each meter. The following options can
be specified now, or added at any time in the future.
Multiple Inputs:
Monitor as many as 24 inputs. The first multiple input card switches six
channels of thermocouples or three channels of RTD or thermistor units.
Maximum of 4 cards per instrument. Order Option: -20 (6 inputs of
thermocouple); -21 (3 inputs of RTD/thermistor).
Math
Expressions: Provides display of maximum, minimum, rate of change or
timed average value of measurements. Front panel keys allow you to view
the math value or switch back to view the actual measured value. Order
Option: -04
Alarms:
Each option card provides two alarms with separate limits and relays. Up
to two cards can be specified. Any combination of high, low or ± values
can be used to trigger the alarm, from either actual or math processed
input. Trigger delay and a settable dead-band are included as standard. Order
Option: -03 (order two for 4 alarms)
Analog Output:
For output to recorders or other analog input instruments, you can
choose from two fully isolated, linearized analog outputs. Both output
types, 4-20mA or 0-10VDC can be fully scaled. Output can be assigned to
direct measurements or to math values. Order Option: -06 (4-20mA);
-05 (0-10VDC)
Digital Output:
Serial Output
RS232C or 20mA interface sends display information in serial ASCII
format. Includes user selectable transmission rates from 300 to 9600
baud, line feed, and carriage return. Order Option: -07
IEEE-488 Output.
For integration with IEEE-488 Bus based measurement or analytical
systems. Main indicator and other options can be programmed via the
IEEE-488 Bus. (Requires two option slots.) Order Option: -08
Differential
measurement. This card provides an additional input channel and the
capability to display the difference (sT) between the two
channels. This option card, -22, can be specified with thermocouple and
voltage input models. The -23 option is specifically for use with RTD or
thermistor configurations.
This function can
be combined with other options: maximum, minimum, and average deltas
when used with math capability, scaled analog output of differentials
when used with analog output, and alarm points based on differential
limits (Cannot be used in same indicator with -20 and -21 options. Not
for use with current loop or strain-gage versions.) Order Option -22
for DELTA and 2 thermocouple or voltage inputs, -23 for DELTA and 2 RTD
or thermistor inputs.
450
Series
±0.1%
Accuracy
1°/0.1°
Switchable
0.1°
Resolution to 399.0°F, 203°C
2000 Hour
Battery Life
Type J, K,
T, E, thermocouples, Platinum RTD or Thermistor
°F/°C
switchable on Front Panel
Data Hold
Made In USA
Digital
Temperature Measurement
Doric provides
complete portable thermometry solutions with meters, probes, and
accessories. If you're looking for fast response coupled with high
repeatability in surface, air, or immersion measurements, you're looking
for a Doric handheld thermometer.
For maximum
performance, pick from among the most accurate, reliable, and convenient
handheld thermometers ever developed — the Series 450 from Doric.
Using a unique,
patented noise-reduction circuit, the Series 450 achieves the high
repeatability and accuracy of line-powered bench top units. A
custom-designed dual IC set gives you a single instrument with wider
temperature ranges, higher resolutions, and longer performance than
other handheld thermometers. Data hold freezes the displayed reading for
safe viewing away from hazardous measurement locations.
Battery life is
unsurpassed, with a single nine-volt battery providing more than 2000
hours of use. An externally available zero pot, conveniently located at
the back of the instrument, lets you match ice point calibrations to
specific probes for even greater system accuracy.
The 450s are
available in thermocouple, RTD, or thermistor configurations. Please
specify when ordering.
Model 450K is for
use with Type K thermocouple probes and provides the fastest response
time over a wide temperature range. Model 450PT is for use with platinum
RTDs, which will provide the greatest system accuracy over a wide range.
The thermistor version, Model 450TH, is a fixed 0.1 F/ C high-resolution
meter and is compatible with thermistor probes that offer high accuracy
in a narrow, low-temperature range. Meter versions are also available
for use with existing Type J, E, and T thermocouples.
For years of
reliable, accurate temperature measurements, get the only handheld
thermometer that measures up to the standards of bench top units — the
Series 450 from Doric.
Range
Table
Model
Sensor
1°C
1°F
0.°C
0.°F
450K
K
T/C
-189°
to +1372°
-308°
to +2501°
-139.8°
to +203.7°
-219.7°
to +398.7°
450E
E
T/C
-212°
to +1006°
-350°
to +1844°
-137.0°
to +203.0°
-215.0°to
+398.0°
450J
J
T/C
-194°
to +1014°
-318°
to +1858°
-117.0°
to +203.5°
-179.4°
to +398.3°
450T
T
T/C
-217°
to +403°
-360°
to +758°
-148.2°
to +203.9°
-234.8°
to +399.0°
450PT
Pt
RTD
-233°
to +904°
-387°
to +1660°
-102.0°
to +203.0°
-152.0°
to +397.0°
450TH
Thermistor
--
--
-25.0°
to +103.0°
-14.0°
to +217.0°
General
Specifications
Accuracy
1°C
Range
1°F
Range
0.1°C
0.1°F
Thermocouple
±0.1%
rdg, ±0.8°C
±0.1%
rdg, ±1.4°F
±0.1%
rdg, ±0.3°C
±0.1%
rdg, ±0.54°F
RTD
±0.1%
rdg, ±0.8°C
±0.1%
rdg, ±1.4°F
±0.1%
rdg, ±0.25°C
±0.1%
rdg, ±0.45°F
Thermistor
±0.1%
rdg, ±0.25°C
±0.1%
rdg, ±0.45°F
Display
0.3" (8mm) LCD
Resolution
1°/0.1°F and °C
Linearization
100% digital in custom ASIC
Reference Junction Tracking
±0.03°/°C, 5-45°C
±0.05°/°F, 41-113°F
Operating Temperature Range
0-50°C/32-122°F
Probe Connection
Thermocouple: Standard sub-mini T/C,
RTD: 3-pin TA3M
Thermistor: 1/4" phone jack
Battery Type/Life
9V NEDA #1604 (included)
Thermocouple: 2000 hours
RTD: 500 hours
Thermistor: 1200 hours
Size
(H x W x D) 5.7" x 3.3" x 1.8"
(144mm x 85mm x 45mm)
Weight
9 oz. (255g)
Warranty
One year
Model 473
Simulates
and Measures Thermocouples, Ohms, Milliamps, and Millivolts
Calibrates
Temperature Controllers, Indicators, Recorders, and Transmitters
Long Battery
Life
Handheld
Versatility
Hi/Lo Memory
Made In USA
Model 475
Simulates
and Measures RTDs, Ohms, Milliamps, And Millivolts
Calibrates
Temperature Controllers, Indicators, Recorders, and Transmitters
Long Battery
Life
Handheld
Versatility
Hi/Lo Memory
Made In USA
Phone:
813-971-5001
Fax : 813-971-5117
Omni
Controls Inc.
5309 Technology Dr.
Tampa, FL 33647
Toll
Free
1-800-783-6664
Sales@Omnicontrols.com
We
guarantee a 24 hour response on all inquiries made via email.
For quicker response please call Omni Controls
at any of the above numbers