Log data
directly to your PC in 1 minute to 24 hour intervals
Dual Alarm
Option with selectable HI/LOW or Deviation Setpoints
Captures
MIN/MAX readings
Scaleable
Analog Output Readings
User-friendly
Alpha Numeric Menu
Made In USA
Programmable
Digital Temperature Indicator and Data Logger
The Doric 5000
Series of single and multiple channel digital temperature indicators
sets a new standard for performance, features, value and reliability.
With built-in programmability, RS232 serial communications and powerful
Windows-based software, the Doric 5000 is ideal for monitoring, testing
and process control applications.
Complete
configuration of the instrument can be quickly performed from the front
panel, including sensor input type, sampling rate, limit settings, and
resolution. Current value and min/max values can be selected for display
from the front panel.
Thanks to its
exclusive Viewer software, the Doric 5000 becomes a powerful PC-based
data gathering, display and logging system. All front panel setup
commands can be executed from your PC and all channel data, limit/alarm
status and min/max values can be viewed simultaneously. In addition, you
can label channel data, perform engineering unit calculations, log data
and create exportable data files.
With the multiple
inputs option installed, the 5000 Series provides simultaneous
monitoring of up to six thermocouple or three RTD channels.
On single input
models, an optional board may be installed which provides enhanced alarm
functions as well as a scalable, linearized 4-20ma/0-10V analog output.
Multiple Inputs
Instead of the
dual alarm/analog output option, the Doric 5000 can be configured to
accept up to six thermocouples or three platinum RTDs.
All active inputs
can be manually selected or automatically scanned. A front panel channel
indicator accompanies the displayed data. Individual limits can be
assigned to each channel. A built-in 5A rated form-C relay is energized
whenever the limit on the selected channel is exceeded.
Analog Output
Analog output
capability is also available in combination with the dual alarm option.
A linearized output (4-20mA or 0-10V) with fully adjustable zero and
span allows the instrument to serve as an indicating transmitter for a
proportional controller, high-level input to a PC-based data converter
or other recording device.
Dual Alarms
With the dual
alarm option installed, the Doric 5000 can be configured to perform
on/off control functions as well as process monitoring. Setpoints can be
set for high, low or deviation. In addition, hysteresis (deadband) and
delay can be programmed into each setpoint. Alarm conditions can be
programmed for manual acknowledgment or for automatic reset. The dual
alarm option comes equipped with two 5A rated form-C (NO/NC) relays, one
for each alarm setpoint and flashing display whenever an alarm condition
exists.
General
Specifications
Size
1/8 DIN, 1.89" (H), 3.78" (W)
Repeatability
±1 Count
Stability with Temperature
Zero: 1µV per °C
Span: 0.01%
Thermocouple Reference Junction
Internal, automatic, 0.03°C per °C, 5°C to 45°C.
Break Detection
Upscale = 50nA, unit displays OL
Stability with Time
0.8° per year
Noise Rejection
NMRR: 60dB at 50-60Hz
CMRR: 120dB at 50-60Hz
(±0.1Hz with 250 unbalance)
Overload Protection
Power leads to ground: (1500VDC or VAC RMS)
Across inputs, for one minute: T/C up to 250VDC or VAC, V+ to V-
Input Impedance
Thermocouple: 20M, exclusive of break detect current effects
RTD: 16.9 K, V+ input to 1 input
RTD Lead Wire Error
At 150µA excitation current: 40m/ of equal resistance in
V+ and V- leads, 1 of imbalance in V+ or V- leads
Point Update Rate
2 per second nominal (1° readings)
1 per second nominal (0.1° readings)
Display
4 Digit, 14-segment red or green, 0.56" height LED
plus one 0.4" green °F/°C LED
Environmental Ranges
Operating: 0° to 50°C
Storage: -40° to +65°C
Humidity: <80% RH non-condensing
Multi-input Option Accuracy
Add ±0.5°C/1°F to instrument accuracy specification
Alarm Relay Contact Rating
5A@ 120VAC (non-inductive load) Form-C
Power
100-240VAC (±10%), 50-400Hz Standard
12VDC, 24VDC 24VAC available
RS232 Serial Communications (Standard) Type: full-duplex voltage, isolated from ground to 500 VAC.
9600 Baud, 8 bits, 1 stop bit, no parity, ASCII.
Thermocouple
Range Table
1°
Resolution
0.1°
Resolution
Sensor
Type
Range/Display
Accuracy(±)*
Range/Display
Accuracy(±)*
J
-337 to
1403°F
-205 to 762°C
1°F+.03%
rdg
1°C+.03% rdg
-99.9°
to 999.9°F
-99.9° to 761.8°C
0.9°
0.5°
K
-331 to
2510°F
-202 to 1377°C
1°F+.03%
rdg
1°C+.03% rdg
-99.9°
to 999.9°F
-99.9° to 999.9°F
0.9°
0.5°
T
-346 to
755°F
-210 to 401°C
1°F+.03%
rdg
1°C+.03% rdg
-99.9°
to 754.6°F
-99.9° to 401.4°F
0.9°
0.5°
E
-338 to
1835°F
-205 to 1002°C
1°F+.03%
rdg
1°C+.03% rdg
-99.9°
to 999.9°F
-99.9° to 999.9°F
0.9°
0.5°
R
+32 to
3216°F
0 to 1769°C
1°F+.05%
rdg
1°C+.05% rdg
S
+32 to
3218°F
0 to 1770°C
1°F+.05%
rdg
1°C+.05% rdg
*Accuracy
±1 digit
RTD
Range Table
1°
Resolution
0.1°
Resolution
Sensor
Type
Range/Display
Accuracy(±)*
Range/Display
Accuracy(±)*
Platinum
RTD
-329 to
1585°F
0.8°,+0.03%
-99.9°
to 999.9°F
0.9°
1003-wire
(0.00385)
-200 to
863°C
0.8°,+0.03%
-99.9°
to 862.6°F
0.5°
Platinum
RTD
-332 to
1563°F
0.8°,+0.03%
-99.9°
to 999.9°F
0.9°
1003-wire
(0.00392)
-202 to
851°C
0.8°,+0.03%
-99.9°
to 862.6°F
0.5°
*Accuracy
percentage of reading +1 digit
5000D-Digital
Process Indicator
and Miniature Datalogger
6 Channel
Scanner Option with selectable scan rates
Accepts 0-10
VDC or 0-20mA and scales from -999 to +9999 cts
Log data
directly to your PC in 1 minute to 24 hour intervals
Captures Min
and Max Readings
Scalable
Analog Output Option
Dual Alarm
Option with Hysteresis, Deviation and Delay
User-friendly
Alpha Numeric Menu
Made In USA
Programmable
Digital Process Indicator and Data Logger
The Doric 5000D of
single and multiple channel digital process indicators sets a new
standard for performance, features, value and reliability. With built-in
programmability, RS232 serial communications and powerful Windows-based
software, the Doric 5000 is ideal for monitoring, testing and process
control applications.
Complete
configuration of the instrument can be quickly performed from the front
panel, including sampling rate, limit settings, and resolution. Current
value and min/max values can be selected for display from the front
panel.
Thanks to its
exclusive Viewer software, the Doric 5000 becomes a powerful PC-based
data gathering, display and logging system. All front panel setup
commands can be executed from your PC and all channel data, limit/alarm
status and min/max values can be viewed simultaneously. In addition, you
can label channel data, perform engineering unit calculations, log data
and create exportable data files.
With the multiple
inputs option installed, the 5000 Series provides simultaneous
monitoring of up to six process input channels.
On single input
models, an optional board may be installed which provides enhanced alarm
functions as well as a scalable, linearized 4-20ma/0-10V analog output.
Multiple Inputs
Instead of the
dual alarm/analog output option, the Doric 5000 can be configured to
accept up to six 0-10 VDC or 0-20mA inputs.
All active inputs
can be manually selected or automatically scanned. A front panel channel
indicator accompanies the displayed data. Individual limits can be
assigned to each channel. A built-in 5A rated form-C relay is energized
whenever the limit on the selected channel is exceeded.
Analog Output
Analog output
capability is also available in combination with the dual alarm option.
A linearized output (4-20mA or 0-10V) with fully adjustable zero and
span allows the instrument to serve as an indicating transmitter for a
proportional controller, high-level input to a PC-based data converter
or other recording device.
Dual Alarms
With the dual
alarm option installed, the Doric 5000 can be configured to perform
on/off control functions as well as process monitoring. Setpoints can be
set for high, low or deviation. In addition, hysteresis (deadband) and
delay can be programmed into each setpoint. Alarm conditions can be
programmed for manual acknowledgment or for automatic reset. The dual
alarm option comes equipped with two 5A rated form-C (NO/NC) relays, one
for each alarm setpoint and flashing display whenever an alarm condition
exists.
General
Specifications
Size
1/8 DIN, 1.89" (H), 3.78" (W)
Accuracy Specification
0.02% RDG +/-1 digit
Sensitivity
Maximum:200uV/Count; 0.4uA/Count
Minimum:1 count
Repeatability
±1 Count
Stability with Temperature
Zero: 1µV per °C
Span: 0.01%/rdg/°C
Noise Rejection
NMRR: 60dB at 50-60Hz
CMRR: 120dB at 50-60Hz
(±0.1Hz with 250 unbalance)
Overload Protection
Power leads to ground: (1500VDC or VAC RMS)
Across inputs, for one minute:
Voltage: up to 250VDC or VAC, V+ to V-
Current: 75mA DC or AC
Input Impedance
Voltage: 1M
Current: 10Point Update Rate
2 per second nominal
Display
4 Digit, 14-segment red, 0.56" height LED
plus one 0.4" green Process (L) or Program (P) mode indicator
Environmental Ranges
Operating: 0° to 50°C
Storage: -40° to +65°C
Humidity: <80% RH non-condensing
Alarm Relay Contact Rating
5A@ 120VAC (non-inductive load) Form-C
Power
100-240VAC (±10%), 50-400Hz Standard
12VDC, 24VDC 24VAC available
RS232 Serial Communications (Standard) Type: full-duplex voltage, isolated from ground to 500 VAC.
9600 Baud, 8 bits, 1 stop bit, no parity, ASCII.
Phone:
813-971-5001
Fax : 813-971-5117
Omni
Controls Inc.
5309 Technology Dr.
Tampa, FL 33647
Toll
Free
1-800-783-6664
Sales@Omnicontrols.com
We
guarantee a 24 hour response on all inquiries made via email.
For quicker response please call Omni Controls