Signet Indicators and Monitors
Description
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
![]() |
The +GF+ SIGNET 5075 Totalizing Monitor is designed for applications requiring simple flow totalization and the indication of flow rate. The 5075 has two 8-digit resettable and permanent totalizers, an open collector output with an adjustable pulse width, and a backlit liquid crystal display with high visibility analog indication. The 5075 Totalizing Monitor measures direct sensor frequencies of 0.5 to 1500 Hz and is compatible with all +GF+ SIGNET flow sensors. The 5075 is independently calibrated, and measures virtually any volumetric unit from ml to acre-feet. |
| Operating Range: | 0.5 Hz to 1500 Hz |
| Power Requirements: | 12 to 24 VAC or 12 to 24 VDC, unregulated, 50-60 Hz, 10W max. |
| Display: | Analog:
Slide in dials 0-2, 4, 6, 8, 10 or 100 Digital: Backlit 2x16 character alphanumeric LCD |
| Additional Functions | Sensor Pulse, Count Pulse, Remote totalizer reset |
| Operating Conditions: | Operating
temperature: -10 degrees C to 55 degrees C Relative humidity: 0 to 95%, non-condensing |
| Accuracy: | +/-0.5% of reading |
| Materials: | Enclosure: ABS
Plastic, NEMA 4X/IP65 Keypad: Silicone Rubber Panel and case gasket: Neoprene Window: Hard-coated polycarbonate |
| Immunity: | EN50082-2 |
| Emissions: | EN55011 |
| Safety: | EN61010-1 |
| Quality Standards: | CE, CSA, UL |
|
|
Part No. |
Description |
|
Basic Unit: |
3-5075 | 5075 Totalizing Monitor |
| Reversible dial face kit included (0-2, 4, 6, 8, 10 and 100) | ||
Accessories: |
3-5000.395 | Splashproof Back Cover Kit |
| 3-5000.598 | Mounting Bracket | |
| 3-5000.399 | Retrofit Adapter Kit | |
| 3-9000.392 | Liquid Tight Connector Kit | |
![]()
SIGNET
5100 Battery Powered Flow Monitor
|
|
+GF+ SIGNET 5100 Battery Powered Flow Monitor
Description
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
sources with the +GF+ SIGNET 5100 Battery Powered Flow Monitor. A
long life lithium battery powers the unit to display independently
calibrated flow rate and totalizer values. Features include
low-battery voltage indication and a "save-mode" to retain
calibration information during battery replacement, as well as
remote totalizer reset. |
| Operating Range: | 5 Hz to 500Hz |
| Power Requirements: | Internal 3.6V Lithium thionyl chloride battery, 4.5 A hr. (4-year nominal life expectancy) |
| Display: | 4 digit numeric LCD flowrate with dual eight digit totalizers |
| Operating Conditions: | Operating
temperature: 23 to 149 degrees F Relative Humidity: 0 to 95%, non-condensing |
| Accuracy: | +/-0.5% of reading |
| Materials: | Enclosure: ABS
Plastic, NEMA 4X/IP65 Keypad: Silicone rubber Panel Gasket: Neoprene Case Gasket: Neoprene Window: Hard-coated polycarbonate |
| Immunity: | EN50082-2 |
| Emissions: | EN55011 |
| Safety: | EN61010-1 |
| Quality Standards: | CE, CSA, UL |
|
|
Part No. |
Description |
||
Basic Unit: |
3-5100 | 5100 Battery Powered Flow Monitor | |
| (Battery and assorted flow unit/multiplier decals included) | |||
Accessories: |
3-5000.395 | Splashproof Back Cover Kit | |
| 3-5000.598 | Mounting Bracket | ||
| 3-5000.399 | Retrofit Adapter Kit | ||
| 3-9000.392 | Liquid Tight Connector Kit | ||
| 7400-0010 | Battery | ||
+GF+ SIGNET 5500 Flow
Monitor
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
The
+GF+ SIGNET 5500 Flow Monitor
is a feature-packed monitor covering a wide range of applications. Dual totalizers are
calibrated independently of the digital analog flow rate. Expand the communication range
of the system by connecting peripheral equipment to the isolated frequency out, the alarm
contact outputs, or the 4-20 mA current output. Packaged in a slim-line housing with NEMA
4X shatter-resistant front panel, the 5500 is the most sophisticated analog monitor
available. |
Application
![]()
| Operating Range: | 0.5 Hz to 10kHz, optically isolated |
| Power Requirements: | 12 to 24 VAC or 12 to 24 VDC, unregulated, 50-60 Hz, 10W max. |
| Display: | Analog: Slide-in
Dials 0-2, 4, 6, 8, 10 or 100 Digital: Backlit 2X16 character alphanumeric LCD |
| Current Output: | 4 to 20 mA,
non-isolated, internally powered Loop impedance: 350 max. @ 12V, 950 max. @ 24V Accuracy: +/-0.1% Update rate: 100 msec. |
| Alarm Contacts: | Two SPDT relays: 5A
@ 30 VDC, 5A @ 125 VAC, or 3A @ 250 VAC max. Hi/Lo/Pulse programmable with adjustable hysteresis |
| Additional Functions: | Sensor Pulse, Count pulse, Remote totalizer reset |
| Operating Conditions: | Operating
temperature: 14 to 131 degrees F Relative humidity: 0 to 95%, non-condensing |
| Accuracy: | +/-0.5% of reading |
| Materials: | Enclosure: ABS
Plastic, NEMA 4X/IP65 Keypad: Silicone rubber Panel and case gasket: Neoprene Window: Hard-coated polycarbonate |
| Immunity: | EN50082-2 |
| Emissions: | EN55011 |
| Safety: | EN61010-1 |
| Quality Standards: | CE, CSA, UL |
|
|
Part No. |
Description |
|
Basic Unit: |
3-5500 | 5500 Flow Monitor |
| Reversible dial face kit included (0-2, 4, 6, 8,10 and 100) | ||
Accessories: |
3-5000.395 | Splashproof Back Cover Kit |
| 3-5000.598 | Mounting Bracket | |
| 3-5000.399 | Retrofit Adapter Kit | |
| 3-9000.392 | Liquid Tight Connector Kit | |
+GF+ SIGNET 5600 Batch Controller--$745
|
|
|
The
+GF+ SIGNET 5600 Batch
Controller was designed specifically for simple, single function batching systems. A
user-selectable menu allows easy configuration of current and relay options. One relay
provides batch in-progress alarming and the other can be used for a two stage shutdown,
overrun alarm, end-of-batch or missing signal alarm. The 5600 can be combined with any
+GF+ SIGNET flow sensor and an appropriate actuator valve/positioner for automated
batching. |
| Operating Range: | 0.5 Hz to 1000 Hz, optically isolated |
| Power Requirements: | 12 to 24 VAC or 12 to 24 VDC, unregulated, 50-60 Hz, 10W max. |
| Display: | Analog: Reversible
dial, 0 to 100% or 100 to 0% Digital: Backlit 2X16 character alphanumeric LCD Batch size: 0 to 999999 engineering units Totalizer: 8-digit resettable and non-resettable |
| Current Output: | 4 to 20 mA,
non-isolated, internally powered Loop Impedance: 350 max. @ 12V, 950 max. @ 24V Accuracy: +/-0.1% |
| Alarm Contacts: | Two SPDT relays: 5A
@ 30 VDC max., 5A @ 125 VAC, or 3A @ 250 VAC Batch: Batch in progress| Option: Two-stage shutdown, overrun alarm, end of batch pulse, missing signal alarm |
| Additional Functions: | EOB pulse, remote start, stop, resume |
| Operating Conditions: | Operating
temperature: 14 to 131 degrees F Relative humidity: 0 to 95%, non-condensing |
| Accuracy: | +/-0.5% of reading |
| Materials: | Enclosure: ABS
Plastic, NEMA 4X/IP65 Keypad: Silicone rubber Panel and case gasket: Neoprene Window: Hard-coated polycarbonate |
| Immunity: | EN50082-2 |
| Emissions: | EN55011 |
| Safety: | EN61010-1 |
| Quality Standards: | CE |
|
|
Part No. |
Description |
|
Basic Unit: |
3-5600 | Batch Controller |
Accessories: |
3-5000.395 | Splashproof Back Cover Kit |
| 3-5000.598 | Mounting Bracket | |
| 3-5000.399 | Retrofit Adapter Kit | |
| 3-9000.392 | Liquid Tight Connector Kit |
+GF+ SIGNET 5700 pH/ORP Monitor--$765
|
|||||||||||||||||||||||||||||||||||||||||||||||
![]() |
Operational simplicity is the most noticeable feature of the +GF+ SIGNET 5700 pH/ORP Monitor. The software automatically identifies the signal from the sensor and presents the correct operating menu for pH or ORP applications. The analog dial provides easy visibility while the alphanumeric LCD shows precise pH and temperature values. Simple push-button programming displays millivolt, pH, and temperature values. Calibration menus feature "Easy-Cal" automatic calibration, including buffer recognition of the most commonly used pH and ORP values.
|
| Operating Range: | pH: 0 to
14, optically isolated Temp: 5 to 148 degrees F ORP: -1,000 to +1,000 mV's, optically isolated |
| Power Requirements: | 12 to 24 VAC or 12 to 24 VDC, unregulated, 50-60 Hz, 10W max. |
| Display: | Analog: Slide-in
dial reversible 0 to 14 pH or +/-1000 mV's Digital: Backlit 2X16 character alphanumeric LCD |
| Current Output: | 4 to 20 mA,
non-isolated, internally powered Loop Impedance: 350 ohm max. @ 12V, 950 ohm max. @ 24V Accuracy: +/-0.1% |
| Alarm Contacts: | Two SPDT relays: 5A
@ 30 VDC max., 5A @ 125 VAC max, or 3A @ 250 VAC Hi/Lo/Pulse programmable with adjustable hysteresis |
| Operating Conditions: | Operating
temperature: 14 to 131 degrees F Relative humidity: 0 to 95%, non-condensing |
| Accuracy: | +/-0.2% of scale |
| Materials: | Enclosure: ABS
Plastic, NEMA 4X/IP65 Keypad: Silicone rubber Panel and case gasket: Neoprene Window: Hard-coated polycarbonate |
| Immunity: | EN50082-1 |
| Emissions: | EN55011 |
| Safety: | EN61010-1 |
| Quality Standards: | CE, CSA, UL |
Part No. |
Description |
|
Basic Unit: |
3-5700 | 5700 pH/ORP Monitor |
| Reversible dial face kit included (0 to 14 pH and -1000 to +1000 mV's) | ||
Accessories: |
3-5000.395 | Splashproof Back Cover Kit |
| 3-5000.598 | Mounting Bracket | |
| 3-5000.399 | Retrofit Adapter Kit | |
| 3-9000.392 | Liquid Tight Connector Kit | |
+GF+ SIGNET 5800 CR
Conductivity/Resistivity Monitor--$785
|
|||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
Wide range and ease of use allow keypad configuration of the +GF+ SIGNET 5800CR Conductivity/Resistivity monitor to your process requirement. Automatic (and programmable) temperature compensation ensures accuracy. The vibration resistant air-core meter offers excellent visiblility, coupled with the accuracy of a backlit liquid crystal display. |
| Operating Range: | Conductance:
0.055 to 400,000 µS Resistance: 10 k ohm to 18.3 M ohm (0.055 to 100 µS) must be performed in solution temperatures from 20 to 100°C Temperature: PT-1000, 32 to 212 degrees F |
| Power Requirements: | 12 to 24 VAC or 12 to 24 VDC, unregulated, 50-60 Hz, 10W max. |
| Display: | Analog: Slide-in
dials 0 to 2, 4, 6, 8, 10, or 100 Digital: Backlit 2X16 character alphanumeric LCD |
| Current Output: | 4 to 20 mA,
non-isolated, internally powered Loop Impedance: 350 ohm max. @ 12VDC, 950 ohm max. @ 24VDC Accuracy: +/-0.1% |
| Alarm Contacts: | Two SPDT relays: 5A
@ 30 VDC max., 5A @ 125 VAC max, or 3A @ 250 VAC Hi/Lo/Pulse programmable with adjustable hysteresis |
| Temperature Comp.: | Programmable 0 to 10%/degrees C |
| TDS Conversion Factor: | Programmable 0.00 to 3.00 µS/ppm (default 2.00) |
| Operating Conditions: | Operating
temperature: 14 to 131 degrees F Relative humidity: 0 to 95%, non-condensing |
| Accuracy: | +/-0.2% of reading |
| Materials: | Enclosure: ABS
Plastic, NEMA 4X/IP65 Keypad: Silicone rubber Panel and case gasket: Neoprene Window: Hard-coated polycarbonate |
| Immunity: | EN50082-1 |
| Emissions: | EN55011 |
| Safety: | EN61010-1 |
| Quality Standards: | CE, CSA, UL |
Part No. |
Description |
|
Basic Unit: |
3-5800CR | 5800CR Conductivity/Resistivity Monitor |
| Reversible dial face kit included (0 tp 2, 4, 6, 8, 10 and 100) | ||
Accessories: |
3-5000.395 | Splashproof Back Cover Kit |
| 3-5000.598 | Mounting Bracket | |
| 3-5000.399 | Retrofit Adapter Kit | |
| 3-9000.392 | Liquid Tight Connector Kit | |
+GF+ SIGNET 5900
Salinity Monitor
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
![]() |
The +GF+ SIGNET 5900 Salinity Monitor offers direct display of salt water concentrations (salinity) from 0 to 80 ppt (parts per thousand). Utilizing proven conductivity measurement techniques the unit offers direct monitoring and control of salt levels via the dual relay and 4 to 20 mA outputs. This industrial package offers a NEMA 4X front face and optional NEMA 4X rear cover for installation in electrical panels or as a stand alone monitor. Calibration is simplified with single point salinity and temperature entry via the 4 button keypad and wet-cal menu sequence. Low voltage DC or AC power requirements make it safe for use in wet areas. |
| Operating Range: | Salinity:
1 to 80 ppt Temperature: 32 to 212 degrees F |
| Power Requirements: | 12 to 24 VAC or 12 to 24 VDC, unregulated, 50-60 Hz, 10W max. |
| Display: | Analog:
Slide in dials 0-2, 4, 6, 8, 10 or 100 Digital: Backlit 2x16 character alphanumeric LCD |
| Current Output | 4 to 20
mA, non-isolated, internally powered Loop impedance: 350 ohm max. @ 12V, 950 max. @ 24V Accuracy: +/-0.1% |
| Alarm Contacts | Two SPDT
relays: 5A @ 30VDC, 5A @ 125 VAC, or 3A @250 VAC max. HI/LO/Pulse programmable with adjustable hysteresis |
| Operating Conditions: | Operating
temperature: 14 degrees F to 131 degrees F Relative humidity: 0 to 95%, non-condensing |
| Accuracy: | +/-2% of reading |
| Materials: | Enclosure: ABS
Plastic, NEMA 4X/IP65 Keypad: Silicone Rubber Panel and case gasket: Neoprene Window: Hard-coated polycarbonate |
| Immunity: | EN50082-2 |
| Emissions: | EN55011 |
| Safety: | EN61010-1 |
| Quality Standards: | CE, CSA, UL NEMA 4X/IP65 Ð Front Panel |
|
|
Part No. |
Description |
|
Basic Unit: |
3-5900 | 5900 Salinity Monitor |
| Reversible dial face kit included (0-2, 4, 6, 8, 10 and 100) | ||
Accessories: |
3-5000.395 | Splashproof Back Cover Kit |
| 3-5000.598 | Mounting Bracket | |
| 3-5000.399 | Retrofit Adapter Kit | |
| 3-9000.392 | Liquid Tight Connector Kit | |
|