SPECIFICATIONS
Display
2 lines, 6 characters each, 1.80″ tall
Display Update Speed
200 ms (5 updates per second)
Accuracy
± 0.03% of calibrated span
Sunlight Readable Bright Display Standard
ElectricalSupply Voltage
VAC: 85 – 265
VDC: 12 – 24
Input Impedence
Voltage Inputs: > 500 kΩ
Current Inputs: 50 – 100 Ω
SPDT Relays
3 A @ 30 VDC / 125/250 VAC resistive loads
1/14 HP (≈ 50 W) @ 125/250 VAC resistive loads
Input Contact/Digital Input
Contact Voltage: 3.3 VDC
Digital Input Logic High: 3 – 5 VDC
Digital Input Logic Low: 0 – 1.25 VDC
Default Logic: Normally Open/Low
Connectivity
Input Options
0-20 mA, 4-20 mA
0-5 VDC, 1-5 VDC, 0-10 VDC, ± 10 VDC
Output Options
4 SPDT Relays
Isolated 4-20 mA
Programming
Programmable Features
Min/Max, Tare, Hold
Multi-scale Input Display (e.g. Level & Volume)
Noise Filter
High/Low Alarms
Alternating Pump Control
Time Delay for Output Relays
Methods
4 Front-panel Push Buttons
MeterView Pro Software (with PC)
Physical
Size
10.63″ x 12.59″ x 4.77″ (270 mm x 319.7 mm x 121.2 mm)
Weight
6.10 lb (2.76 kg)
Environmental
Front panel rating
NEMA 4X, IP65
Storage Temperature
-40° – 185°F (-40° – 85°C)
Operating Temperature
-40° – 150° F (-40° – 65°C)
Certification
CE
UL/C-UL Listed