SPECIFICATIONS
Display
2 lines, 6 characters each, 1.80″ tall
Display Update Speed
200 ms (5 updates per second)
Accuacy±0.03% of calibrated span
Sunlight Readable Bright Display Standard
Front panel rating
NEMA 4X, IP65
Storage Temp
-40° to 185° F (-40° to 85° C)
Operating Temp
-40° to 149° F (-40° to 65° C)
Programmable Features
Min/Max, Tare, Hold
Multiscale Input Display (e.g. Level & Volume
Noise Filter
High/Low Alarms
Alternating Pump Control
Time Delay for Output Relays
Methods
4 Front-panel Push Buttons
MeterView Pro Software (with PC)
Size
10.63: x 12.59″ x 4.77″ (270 mm x 319.7 mm x 121.2 mm)
Wight
6.10 lb (2.76 kg)
Input Options
0-20 mA, 4-20 mA
0-5 VDC, 1-5 VDC, 0-10 VDC, ±10 VDC
Output Options
2 or 4 SPDT Relays
Isolated 4-20 mA
CE
Ul/C-UL Listed
Supply Voltage
VAC: 85-265
VDC: 12-24
Input Impedence
Voltage Inputs > 500 kΩ
Current Inputs: 50-100 Ω
SPDT Relays
3 A @ 30 VDC / 125/ 250 VAC resistive loads
1/14 HP (≈ 50 W) @ 125/250 VAC inductive loads
Input Contact/Digital Input
Contact Voltage: 3.3 VDC
Digital Input Logic High: 3-5 VDC
Digital Input Logic Low: 0-1.25 VDC
Default Logic: Normally Open/Low