The Megger 246004 BITE 2P Battery Impedance Tester with Built-In Printer determines the condition of lead-acid and nickel-cadmium cells up to 7000 Ah. An advanced feature set has been developed that includes Pass/Warning/Fail calculations based on a user-entered baseline value, advanced printing functions, and more. The case of the BITE 2P consists of both the transmitter and a carrying case for all of the standard accessories and some of the optional accessories, in an all-in-one unit.
The 246004 BITE 2P Battery Impedance Tester works by applying a test current across the battery string while on-line, then measuring the total current (AC ripple and test current) and the voltage drop of each cell/jar. It then calculates the impedance. The BITE 2P also measures DC voltage and interconnection (strap) resistance to help determine the overall condition of the entire battery string’s electrical path from terminal plate to terminal plate.
The receiver of the BITE 2P stores the readings in its internal memory. These measurements, along with other maintenance data such as ambient and pilot cell temperatures and AC ripple current, assist in determining the overall condition of battery systems. Impedance measurements with the BITE 2P may be made part of a battery maintenance program with readings taken and recorded semi-annually for flooded batteries and quarterly for VRLA.
Unlike load cycle testing that involves substantial downtime and repeated discharges, using the instruments require no battery discharge, nor do they stress the battery in any way compared to other techniques. With a test time of less than 20 seconds for each cell and intercell connector, one person can easily, quickly, and precisely measure internal cell impedance, DC terminal voltage and intercell connection resistance without taking the battery system off line.
Everything you need to perform these tests is included with the BITE 2P instrument. There also is a full line of optional accessories to enhance the capabilities of the tester. Furthermore, the BITE 2P has the ability to download readings to a PC for data interpretation. The BITE 2P additionally has a built-in printer to review the active test and also to leave a hard copy record at the site.
Applications
Determine maintenance needs, including:
- Cell replacement criteria based on impedance trends
- Jumpering out a cell or two
- Clean and/or retorque intercell connectors
- Shorten the maintenance interval
Test typical installations, including:
- Electrical power generation plants
- Substations: utility, railroad, industrial
- Telecommunications facilities: CO, Wireline, Wireless, MTSO
- UPS systems
- Railroad: Signals and Communications, substation
- Aircraft power supplies
- Marine, military